The VFD For Pump Control is an electronic device that can control the operating frequency of motors and other equipment. It usually works through AC-DC-AC conversion circuits and changes the power supply frequency according to a specific formula to control the motor speed.
It has speed regulation, energy saving, soft start and multiple protection functions. It can smoothly adjust the motor speed, adjust the power as needed, reduce the start-up impact and ensure the safety of the equipment.
It has a wide range of applications, covering industrial equipment, HVAC, transportation vehicles, household appliances and other fields, which can improve efficiency, save energy and improve performance.The PDM30 model VFD For Pump Control is more suitable for installation on a horizontal multistage centrifugal pump to form a horizontal variable frequency pump.
Features of VFD For Pump Control
Fashion appearance:
- ABS flame-retardant shell
- Curved design, simple and elegant
- Humanized keyboard design, easy to operate
- Integrated design, more fitting appearance
Enhanced algorithm:
- Enhanced PID algorithm
- Super quiet
- Advanced accessories, safe and stable
- Optimized current sampling scheme
Extended communication:
- RS485 communication interface as standard
- Can connect multiple units
- Compatible with current and voltage analog input
Efficient heat dissipation:
- Sunk heat dissipation structure
- Fast heat dissipation
- High-quality fan
Control characteristics
- Control mode: V/F control
- Starting torque: 1Hz 100%
- Speed adjustment range: 1:20
- Speed accuracy: ±1.0%
- Carrier frequency: 0.5kHz~16kHz
- Overload capacity: 120% rated current for 60s, 150 rated current for 1s
Motion Control
- Input voltage: 220V; Fluctuation range: ± 15%
- Input frequency: 50/60Hz, fluctuation range: ± 5%
- Output voltage: 0-input voltage, error less than 5%
- Output frequency: V/F: 0-100Hz
- Operation command channel: 3 channels: operation panel given, control terminal given, serial communication port given, can be switched in a variety of ways
- Frequency source: analog voltage given, analog current given, serial communication given, etc., can be switched in a variety of ways
- Analog power supply: 5V~+24V three power supply voltages, use most sensors
- Input terminals: 3 digital input terminals; 2 modular input terminals; 2 communication terminals, RS485 one channel, CAN one channel
- Output terminals: 2 digital input terminals, 1 module input terminal
Basic Functions
- Built-in PID: can easily realize closed-loop control system
- AVR function: when the grid voltage changes, it can automatically keep the output voltage constant
- Overvoltage and overspeed loss: automatically limit the current and voltage during operation to prevent frequent overcurrent and overvoltage tripping
- Fast current limiting function: minimize overcurrent faults and improve system stability
- Power-on peripheral equipment safety self-check: can realize safety detection of powered peripheral equipment such as grounding, short circuit, etc.
- Power-on automatic start function: power-on automatic start is optional, start delay is adjustable
- Automatic energy saving function: automatically reduce the output voltage under light load to achieve energy saving effect
- Constant voltage control function: PID adjustment, PID feedback disconnection check, PID sleep and wake-up
- Multi-connection working mode: multiple units can be connected through the connection terminal. Realize multi-pump connection mode
- Upper computer communication function: remote equipment maintenance can be performed through an external GPRS monitoring module
- Anti-freeze function: frequency, time, and cycle can be set for anti-freeze function control
- Water leakage detection: optimize sleep control through water leakage detection coefficient
Usage Environment
- Place of use: can be used indoors and outdoors, prevent direct rain, no corrosive gas, flammable gas on site
- Altitude: below 1000m; above 1000m, use with derating, 1% for every 100m increase
- Ambient temperature: -10℃ ~40℃, derating is required when the temperature exceeds 40, 1% for every 1% increase in ambient temperature, the maximum ambient temperature is 50℃
- Humidity: 95%RH, avoid condensation
- Vibration: vibration acceleration is less than 0.6g
- Storage temperature: -25℃ ~ +60℃
Installation process of VFD For Pump Control




Model list
Voltage | Model | Power | Size | Motor | Explanation | ||
---|---|---|---|---|---|---|---|
(kW) | H | W | D | (kW) | |||
220V Single enetry Three out |
PDM30-2SR75-E | 0.75 | 210 | 146 | 121 | 0.75 |
The factory default is 2.2kW,
which can be adjusted by P1-12,
0 = 0.75kW
1 = 1.5kW
2 = 2.2kW
|
PDM30-2S1R5-E | 1.5 | 210 | 146 | 121 | 1.5 | ||
PDM30-2S2R2-E | 2.2 | 210 | 146 | 121 | 2.2 |
Operation Panel
- Operation and display mode
- Status display mode:
When power on the SPD, it enters the status display mode. When it stops, it displays pressure setting. Press "+" or "-"to modify pressure setting. When it is running,it displays current pressure, operating frequency, and setting pressure. Press the "+" or "-" to switch the display; press "MENU" for two seconds to enter the parameter setting mode.
- Parameter setting mode:
To view or set the parameters, as starting from status display mode, press the "MENU" for 2 seconds to enter the parameter setting mode, and then press the "RUN / STOP" starts to set parameters. After you set the parameter press twice "MENU" to exit parameter setting mode, and return to the status display mode.
- The alarm display mode:
Automatically enter this mode when a drive fault or warning arises; press the "RUN / STOP" to reset, or it can automatically restored the previous mode after the alarm is eliminated.
- Menu Operation
Three-class menus are:
- Function group (first class)
- Function code setting(second class)
- Function code setting(third class)
Instruction of vfd for pump control: In the third class menu, pressing "MENU" or "RUN/STOP" can return to the second class menu. The difference is that pressing "RUN/STOP" first saves parameters to control board, and then returns to the second class menu and shifts to next function code automatically; pressing "MENU" returns to the second class menu directly without saving parameters and keeps staying at current function code.
Under the third class menu, only flicker bit can be modified. Revisable bit will shift automatically after 5 seconds.
Note: For parameters marked with "●", please modify them in stopped state. Parameters marked with "◎" are actual detected and recorded values which can't be modified.
Name | Definition and operating instructions |
---|---|
"MENU" button | Click on the 0 level menu to view the role of the parameter for shifting, long press 2S to enter the 1 level parameter setting menu; |
"RUN / STOP" button | Click run / stop / reset in level 0 menu; click confirm in 1/2/3 / level password input menu; |
"UP" button | Click the 0 level menu to increase the set pressure, frequency, modify the parameter value, long press to increase quickly; |
"DOWN" button | Click the 0 level menu to decrease the set pressure, frequency, modify the parameter value, long press to quickly decrease; |
"Target pressure" Indicator | When the display shows "target pressure" and "current pressure", it lights up when the pressure is adjusted; |
"Current pressure" Indicator | When the display is "target pressure" and "current pressure" light up; |
"Running" lights | Always on during operation, blinking during sleep, and extinguished when stop fault; |
"Alarm" indicator | Blinks during faults and goes off when it is not in a fault state; |
"Manual" indicator | When P0-44 = 1 speed control mode, the indicator light is on, other modes are off; |